See detailDecentralized tap changer blocking and load shedding against voltage instability: prospective tests on the RTE system
Capitanescu, Florin ULg; Otomega, Bogdan; Lefebvre, Hervé et al

in International Journal of Electrical Power & Energy Systems (2009), 31(9), 570-576

This paper reports on prospective tests of a system protection scheme against long-term voltage instability relying on a set of distributed controllers, each monitoring a transmission voltage, blocking ... [more ▼]

This paper reports on prospective tests of a system protection scheme against long-term voltage instability relying on a set of distributed controllers, each monitoring a transmission voltage, blocking tap changers and shedding loads in a zone. The emergency actions adjust in magnitude and location to the disturbance. Each controller acts in closed-loop, which guarantees robustness. The method is illustrated on a real-life model of the Western region of the RTE system. The choice of the controller settings is discussed in some detail and examples of performance are given, combining the above remedial action with capacitor switching and secondary voltage control. [less ▲]

Detailed reference viewed: 165 (14 ULg)
Full Text
Peer Reviewed
See detailPROSPECTS OF AN IMPROVED SYSTEM PROTECTION SCHEME AGAINST VOLTAGE INSTABILITY IN THE RTE SYSTEM
Capitanescu, Florin ULg; Otomega, Bogdan; Lefebvre, Hervé et al

(2008, July)

This paper reports on prospective tests of a system protection scheme against long-term voltage instability relying on a set of distributed controllers, each monitoring a transmission voltage, blocking ... [more ▼]

This paper reports on prospective tests of a system protection scheme against long-term voltage instability relying on a set of distributed controllers, each monitoring a transmission voltage, blocking tap changers and shedding loads in a zone. The emergency actions adjust in magnitude and location to the disturbance. Each controller acts in closed loop, which guarantees robustness. The method is illustrated on a real-life model of the Western region of the RTE system. The choice of the controller settings is discussed in some detail and examples of performance are given, combining the above remedial action with capacitor switching and secondary voltage control. [less ▲]

Detailed reference viewed: 81 (7 ULg)
Full Text
Peer Reviewed
See detailReverse-logic control of load tap changers in emergency voltage conditions
Otomega, Bogdan; Sermanson, Vincent; Van Cutsem, Thierry ULg

(2003, June 26)

This papers deals with the emergency control of Load Tap Changers (LTCs) to face low transmission voltages or voltage instability situations. The proposed simple control logic consists in reverting the ... [more ▼]

This papers deals with the emergency control of Load Tap Changers (LTCs) to face low transmission voltages or voltage instability situations. The proposed simple control logic consists in reverting the tap movements once the voltage at a monitored transmission bus falls below some threshold. A deadband on this voltage allows the system to settle down in between the normal and reverse logic modes. In order to control a large number of LTCs, the latter are divided into clusters, each with its own monitored voltage. The paper also considers the control of two levels of LTCs in cascade, where proper coordination is required between the two levels. The proposed scheme has been tested on a detailed EHV-HV-MV planning model of the Western region of the French transmission system operated by RTE. Long-term time responses to major disturbances are shown to illustrate the performance of the proposed scheme. [less ▲]

Detailed reference viewed: 51 (5 ULg)
Full Text
Peer Reviewed
See detailAn advanced tool for Preventive Voltage Security Assessment
Van Cutsem, Thierry ULg; Capitanescu, Florin ULg; Moors, Cédric et al

(2000, May)

This paper deals with methods for the preventive assessment of voltage security with respect to contingencies. We describe a computing tool for the determination of secure operation limits, together with ... [more ▼]

This paper deals with methods for the preventive assessment of voltage security with respect to contingencies. We describe a computing tool for the determination of secure operation limits, together with methods for contingency filtering. Examples from two very different real-life systems are provided. We outline extensions in the field of preventive control. [less ▲]

Detailed reference viewed: 85 (6 ULg)
Peer Reviewed
See detailVoltage security assessment of systems with multiple instability modes
Sermanson, Vincent; Moisse, Christel; Van Cutsem, Thierry ULg et al

in Proc. 4th Intern. Workshop on Bulk power systems dynamics and control (Restructuring) (1998, August)